3BUS 208 000 R1301 75Platform Tuning
Uploading Parameters
This operation is used to prepare a new Motor Drive Panel unit with default
parameters from a Motor Drive that is known to have the correct operational
parameters installed.
Note: Make sure:
1. The configuration switch (S1) on the motor controller is at zero
(0).
2. The MDPanel is showing LOCAL mode.
1. Press the MENU push button to get to the group display.
2. Press the UP arrow push button until the display shows “-UL-”.
Do not execute the -Fd-” menu selection. It will change
the Motor Drive to the ABB Drives factory settings, not
the settings established for the Smart Platforms.
3. Press and hold the ENTER push button until the display starts to blink. When
the operation is complete, the display will revert back to the power-up display
of output frequency (Hz).
4. Return the MDPanel to REMOTE operation when done.